Product Features

1.Copper paint spray sealing on welding port/soldering point surface, highly anti-rusting & deeply balancing uneven tension by poor welding.
2.Meticulous heat preservation process. High-quality thermal insulation tape combines with high-density Polyeaster rubber-plastic thermal insulation foam, conducting 360°thermal insulation around components & pipes, heat loss in 24H is <4℃ & seals much noise.
3.TWO solders high-temp. welding, fully improving welds’ strength to reduce gas leakage. Mysteriouse flux miraculously improves auxiliary heat conduction, removing oxides, reducing welded surface tension & increasing the area, preventing re-oxidation &>2-time prolonging pipeline’s life.
4.”Pressure Sensor” takes place of Pressure Gauge, not easy to frost, with “pressure”, “water flow” & more real-time data can indicates in LED screen.


Parameter

Model | ADC-20HC | ADC-22HC | ADC-26HC | ||
HP | 6HP | 7HP | 8HP | ||
Power Supply | 380-415V/50-60Hz/3ph | ||||
Heating Condition: Ambient Temp. +7℃/+6℃(WB/DB), Water Temp. +30℃/+35℃(In/Out). | |||||
Heating Capacity Rang | kW | 4.81-16.05 | 6.24-18.85 | 6.43-21.57 | |
Power Input Range | kW | 0.78-3.7 | 0.96-4.08 | 1.04-4.85 | |
Hot Water Condition: Ambient Temp. +20℃/+15℃ (DB/WB), Water Temp. +15℃/+55℃ (In/Out). | |||||
Heating Capacity Rang | kW | 5.35-19.25 | 6.74-22.66 | 6.97-25.95 | |
Power Input Range | kW | 1.06-3.98 | 1.33-4.67 | 1.44-5.45 | |
SCOP | at 35℃ water outlet | 4.84 | 4.82 | 4.85 | |
at 55℃ water outlet | 3.53 | 3.45 | 3.54 | ||
ErP Level | at 35℃ water outlet | A+++ | A+++ | A+++ | |
at 55℃ water outlet | A++ | A++ | A++ | ||
Heating operation range | Ambient | °C | -30~25 | ||
Heating side | °C | 18~60 | |||
Domestic hot water operation range | Ambient | °C | -30 ~ 43 | ||
Water side | °C | 25~60 | |||
Chilling Condition: Ambient Temp.35℃/30℃ (DB/WB), Water Temp.12℃/7℃(In/Out). | |||||
Chilling capacity | kW | 3.24-13.37 | 4.37-15.95 | 4.83-18.56 | |
Power input range | kW | 1.38-4.67 | 1.57-5.46 | 1.65-6.23 | |
Chilling operation range | Ambient | °C | 10~43 | ||
Water side | °C | 7~22 | |||
Rated water flow rate | m³/h | 2.58 | 2.93 | 2.95 | |
Rated pressure drop | kPa | 45 | 45 | 47 | |
Max. working pressure | Refrigerant | Bar | 44 | 44 | 44 |
Water | Bar | 7 | 7 | 7 | |
Controller | Micro processor based digital wire controller, LCD Touch Screen | ||||
External cabinet | Galvanized steel with powder coating | ||||
Compressor | Type | Panasonic Dual Rotary | |||
Refrigerant | R32 | ||||
Water heat exchanger | SUS 316 Brazed plate heat exchanger | ||||
Water pipe | Inlet&Outlet | DN | 25 | 25 | 32 |


Detailed image

Working Principle

1. Compressor | 2 Four-way valve | 3 Tube in tube heat exchanger | 4 Pressure drop switch |
5 Water pump | 6 Filter drier | 7 EVI heat exchanger | 8 EEV |
9 EVI EEV | 10Fin/tube heat exchanger | 11 Gas-Liquid Separator | 12 Low – pressure switch |
13.High – pressure switch | 14. Refrigerant accumulator |
SG ready

SG ready Control logic
SG Grid Signal [LDIsg] | EVU Supply Signal [LDIevu] | Smart Grid Command | Smart Grid Display |
0 | 1 | Smart Grid Directive 1 | Display low-peak power consumption icon |
0 | 0 | Smart Grid Directive 2 | Display peak power icon |
1 | 0 | Smart Grid Directive 3 | Indicates free electricity icon |
1 | 1 | Smart Grid Directive 4 | Indicates free electricity icon |